LED display power supply system leakage protector frequent trip reasons

Aug 09, 2017

Leave a message

led display .jpg

1, leakage protector layout is unreasonable


    As the LED display installation site has the particularity, such as wiring error, line damage, switch box leakage protector damage, some electrical appliances have not been through the switch box and other reasons, as well as leakage protection itself is inevitable Moving, coupled with the actual situation in accordance with the actual use of electrical leakage protection device layout, resulting in frequent leakage protection device frequent trip.


    In addition to strengthening the management of this situation, but also from the technical point of view, according to the actual situation of the leakage protection device for a reasonable layout. The total leakage protection on the incoming power supply can be mainly used as a total protection for preventing electrical fires and electrical short circuits. It also provides the backup protection for each small leakage protection range. Its rated leakage current can be in the range of 200 ~ 500mA Between the choice of rated leakage action time can choose 0.2 ~ 0.3s. In this way, can greatly reduce the surge voltage, inrush current, electromagnetic interference on the total leakage protection, improve the overall leakage protection action selectivity and reliability. If you can make each leakage protection within the scope of the secondary leakage protection in an effective protection of the state, you can greatly reduce the site of the total leakage protection of the frequent tripping probability.


    2, within the scope of protection did not form an effective two or three leakage protection


    The last type of leakage protection in the switch box is the main protection of the electrical equipment, if the final leakage protection device is not installed, damaged or improper selection, it may lead to frequent leakage protector overload. As the led display a lot of metal conductors, wire connectors are more, if the wire insulation is not very good, it will lead to frequent leakage of the situation; some also added some sockets, in many cases do not install leakage protector, often caused leakage The Only in each protection within the scope of the formation of an effective two or three leakage protection mode, in order to effectively reduce the frequent leakage of leakage protection.


3, leakage protector itself has some limitations


    (1) the current leakage protector, whether electromagnetic or electronic type are using magnetic induction voltage transformer pick up the main circuit in the leakage current, three-phase or three-phase four-wire in the magnetic ring can not be fully balanced layout. LED display of the three-phase power load can not be fully balanced in the high current or higher over-voltage, will have a high magnetic permeability in the magnetic induction of a certain electromotive force, the electromotive force to a certain extent , It will lead to leakage protector tripping. As the rated current of the larger leakage protection using a relatively large magnetic ring, the leakage flux is also relatively large, and the leakage current to overcome the magnetic force of the magnetic ring itself, resulting in the actual use of the leakage current rating of the larger , The lower the sensitivity, the greater the rate of rejection.


    (2) leakage protection device in the rated leakage current and the rated leakage current does not have an action between the uncertainty of the area, the leakage current leakage in the protection of this area may cause the leakage protection device without tripping.


4, leakage protector selection is unreasonable


    (1) the use of the switch box within the rated leakage current exceeds 30mA or more than twice the rated current of the electrical equipment leakage protection device, or the use of a delay with the type of leakage protection device, due to the rated leakage current Improve or protect the sensitivity of the decline, the occurrence of leakage failure, the final leakage protector no action, the higher leakage protection device may be action.


    (2) to the LED display power when the starting current is often relatively large, this high current may make the leakage protector tripping. Therefore, as far as possible to batches to the display of the box power. In addition, the general should be used on the over-voltage, over-current is not sensitive to the electromagnetic leakage protector; or select the rated current 1.5 to 2 times larger than the electronic leakage protection, but as the final leakage protection, rated leakage action The current should not be greater than 30mA.


    In short, the frequent leakage of leakage protection device is the result of a combination of various factors, the most important thing is to properly arrange the leakage protector, reduce the protection of two or three types of leakage protection, the correct choice of leakage protector and wiring, so that each The scope of the two or three leakage protection device is in an effective state of protection; the other is to strengthen the management of electricity and through training to improve the quality of their own people to prevent non-electrical wiring, so that you can not only improve the safety of electricity, And can reduce the frequent leakage of the leakage protector to the LED display of the normal work to create a better power supply conditions.